On-roof fitting and installation 4
0020077994_02 auroTHERM exclusive Installation manual 15
Conditions: Parallel connection
▶ To avoid pressure losses in the sub-collector fields, only
use parallel connection for collector rows with the same
number of collectors.
▶ Ensure that each sub-collector field has the same total
tube length in the flow and return (Tichelmann system),
in order to avoid pressure losses in the connection tubes.
4.1.4 Preparing the roof duct
Caution.
Building damage due to penetrating wa-
ter.
If the roof duct is not prepared properly,
water may penetrate the building interior.
▶ Ensure that the roof duct is prepared
properly.
1. Make a v-shaped cut in the roofing felt membrane.
2. Fold the upper, wider flap onto the roof batten above,
and fold the lower, narrower flap onto the roof batten
below.
3. Fix the roofing felt membrane tight to the roof batten,
so that any moisture runs off to the side.