For the installer
24/2 E
28/2 E
GB
Instructions for Installation and Servicing
turboMAX pro
Wall hung room sealed fan assisted
combination and system boilers
833792_41GB_012005.qxd 09.03.2005 16:47 Uhr Seite 1
Vista de pagina 0
1 2 3 4 5 6 ... 43 44

Indice de contenidos

Pagina 1 - For the installer

For the installer24/2 E28/2 EGBInstructions for Installation and ServicingturboMAX proWall hung room sealed fan assisted combination and system boiler

Pagina 2 - Table of Contents

4 General RequirementsInstructions for Installation and Servicing turboMAX pro R310Important!This appliance must be earthed.4.8 Guide to system requir

Pagina 3 - List of contents 1

General Requirements 4Instructions for Installation and Servicing turboMAX pro R3 114.8.6 Circulating pumpThe circulating pump is included in the boil

Pagina 4 - 2 Introduction

Fig. 5.2: Free space required for installationSelecting position of boilerRefer to „Boiler location“ for information regarding sit-ing the appliance.

Pagina 5 - Boiler Specification 3

Boiler Installation Sequence 5Instructions for Installation and Servicing turboMAX pro R3 135.2 Using boiler templateFix the paper template to the wal

Pagina 6 - 3 Boiler Specification

5.7 Gas supply• Connect the 15 mm compression gas service cock (1)supplied with the appliance (2) and tighten.• Connect a gas supply pipe of not less

Pagina 7

Boiler Installation Sequence 5Instructions for Installation and Servicing turboMAX pro R3 155.8 Cold water mains inlet and hot water outletFlush all f

Pagina 8

5 Boiler Installation SequenceFig. 5.9: Wiring systemFig. 5.10: Exposed rear view of switchgear cabinet• Connect the power supply cord as follows (Fig

Pagina 9

Boiler Installation Sequence 5Instructions for Installation and Servicing turboMAX pro R3 17Abb. 0.0 BildunterschriftFig. 5.11 Connection wiringNL987F

Pagina 10 - 4 General Requirements

5 Boiler Installation SequenceConnection details for external time switches andboiler terminal strip.Fig. 5.13 shows the connection details where a ti

Pagina 11 - General Requirements 4

Boiler Installation Sequence 5Instructions for Installation and Servicing turboMAX pro R3 19Fig. 5.14Thermostatic radiator valvesThe boiler has a buil

Pagina 12

Table of ContentsInstructions for Installation and Servicing turboMAX pro R321 List of Contents . . . . . . . . . . . . . . . . . . . . . 31.1 Cont

Pagina 13

6 Commissioning Part IInstructions for Installation and Servicing turboMAX pro R3206 Commissioning Part I6.1 Preliminary electrical checksCheck the el

Pagina 14

Gas supply adjustments (Commissioning Part II) 7Instructions for Installation and Servicing turboMAX pro R3 217 Gas supply adjustments7.1 Gas inlet wo

Pagina 15

7 Gas supply adjustments (Commissioning Part II)Instructions for Installation and Servicing turboMAX pro R322Set the DHW temperature control to maximu

Pagina 16 - RT 24V 230V RT 230V

Gas supply adjustments (Commissioning Part II) 7Instructions for Installation and Servicing turboMAX pro R3 23Burner Pressure turboMAX pro 24/2 EDeliv

Pagina 17 - 5.13 Electronic board layout

7 Gas supply adjustments (Commissioning Part II)Instructions for Installation and Servicing turboMAX pro R3247.5 Fit combustion chamber coverCarefully

Pagina 18

Functional Checks (Commissioning Part III) 8Instructions for Installation and Servicing turboMAX pro R3 258 Functional Checks 8.1 Functional checksPro

Pagina 19 - Fig. 5.14

8 Functional Checks (Commissioning Part III)Instructions for Installation and Servicing turboMAX pro R3268.3 Adjusting pump speedThe unit is fitted wi

Pagina 20 - 6 Commissioning Part I

Servicing 9Instructions for Installation and Servicing turboMAX pro R3 279 Servicing9.1 Initial InspectionTo ensure the continued safe and efficient o

Pagina 21 - 7 Gas supply adjustments

9 ServicingInstructions for Installation and Servicing turboMAX pro R3289.2 Cleaning the burner and primary heat exchanger• Turn off the boiler.• Isol

Pagina 22

Fault Finding 10Instructions for Installation and Servicing turboMAX pro R3 29To reset the appliance after a lockout (either burnerlockout illuminate

Pagina 23

List of contents 1Instructions for Installation and Servicing turboMAX pro R3 31 List of contents1.1 Contents included with boilerEnsure that all con

Pagina 24 - Fig. 7.4: Fit boiler casing

10 Fault FindingInstructions for Installation and Servicing turboMAX pro R330Ensure boiler mainON/OFF control is setto position "1" Yes Go t

Pagina 25 - Fig. 8.2 Functional check

Fault Finding 10Instructions for Installation and Servicing turboMAX pro R3 31Sheet BCheck operation of pump and fanTurn off the main ON/OFF control t

Pagina 26 - Fig. 8.3: Pump speed

10 Fault FindingInstructions for Installation and Servicing turboMAX pro R332Check central heating and controlsEnsure that radiator temperature contro

Pagina 27 - Servicing 9

Fault Finding 10Instructions for Installation and Servicing turboMAX pro R3 33Does fan run after approx. 30 secs.?Check flue and ignition systemNoChec

Pagina 28 - 9 Servicing

10 Fault FindingInstructions for Installation and Servicing turboMAX pro R334Check gas valve and central heating system pressureDoes burner light 1sta

Pagina 29 - Fault Finding 10

Fault Finding 10Instructions for Installation and Servicing turboMAX pro R3 35Does flame indicator glow andflames increase in size to full gasrate aft

Pagina 30 - 10 Fault Finding

10 Fault FindingInstructions for Installation and Servicing turboMAX pro R336Draw hot water at high rate YesCheck hot water flow rate and temperature.

Pagina 31

Diagrams 11Instructions for Installation and Servicing turboMAX pro R3 37power supplyF2AL2N1main switchmaintransformer230V20VairpressureswitchfanpumpN

Pagina 32

11 DiagramsInstructions for Installation and Servicing turboMAX pro R338Switchgear cabinetU100X3T 2= F2T 1,25 = F3X2X2X1242311213141516171819202122234

Pagina 33

833792_41GB_012005.qxd 09.03.2005 16:47 Uhr Seite 39

Pagina 34

2 Introduction2.1 General InformationNote!This boiler must be installed and serviced by acompetent person in accordance with the GasSafety (Installati

Pagina 35

833792_41GB_012005.qxd 09.03.2005 16:47 Uhr Seite 40

Pagina 36 - Check D.H.W operation

833792_41GB_012005.qxd 09.03.2005 16:47 Uhr Seite 41

Pagina 37 - Diagrams 11

833792_41GB_012005.qxd 09.03.2005 16:47 Uhr Seite 42

Pagina 38 - Switchgear cabinet

833792_41GB_012005.qxd 09.03.2005 16:47 Uhr Seite 43

Pagina 39

833792_42 GB R3 03 2005 Subject to alteration833792_41GB_012005.qxd 09.03.2005 16:47 Uhr Seite 44

Pagina 40

Boiler Specification 3Instructions for Installation and Servicing turboMAX pro R3 5turboMAX pro 24/2 E turboMAX pro 28/2 E Units(VUW GB 242/2-3) (VUW

Pagina 41

3 Boiler SpecificationInstructions for Installation and Servicing turboMAX pro R363.3 Functional DiagramFig. 3.2: Functional Diagram1 Air duct2Fan3 Ma

Pagina 42

General Requirements 4Instructions for Installation and Servicing turboMAX pro R3 74 General Requirements4.1 Related DocumentsThe installation of the

Pagina 43

4 General Requirements4.4.2 Rear outlet flue system (100 mm outside diameter)The rear outlet horizontal flue system (Art. No. 303 817)is suitable for

Pagina 44

General Requirements 4Instructions for Installation and Servicing turboMAX pro R3 94.4.4 Flue terminationThe following details refer to both flue syst